      JH6000HQ-D4 series  SF6 mixed gas comprehensive detector
      • JH6000HQ-D4 series  SF6 mixed gas comprehensive detector

      JH6000HQ-D4 series SF6 mixed gas comprehensive detector

       ?
      recommendation index:
      Detection function, high accuracy, good stability
      Portable design, fast testing, low air consumption, environmentally friendly
      Automatic flow control, efficient and accurate, effectively reducing sample gas emissions
      Users can use standard gas to self-calibrate the instrument
      • Detect the main decomposition products of insulation material cracking inside SF6 mixed gas electrical equipment: SO2 ,SOF2 , H2 S,CO,NO, N2 O,NF3 ,HF and other contents

      • Detect SF6 purity, SF6/N2 or SF6/CF4 mixing ratio, gas humidity in SF6 electrical equipment

      • JH6000HQ-D4 series SF6 mixed gas comprehensive detector, including JH6000HQ1-D4 (SF6/N2), JH6000HQ2-D4 (SF6/CF4) and JH6000HQ3-D4 (SF6/N2, SF6/CF4) and other models

      • NO, N2O, NF3 are optional

      name

      component

      parameter

      Model

      JH6000HQ1-D4

      JH6000HQ2-D4

      JH6000HQ3-D4

      minimum detectable quantity

      SO2+SOF2、H2S、HF

      ≤0.1μL/L

      CO、NO、N2O、NF3

      ≤0.5μL/L

      SF6

      ≤0.01%

      N2

      ≤0.01%

      \

      ≤0.01%

      CF4

      \

      ≤0.01%

      ≤0.01%

      O2

      ≤0.001%

      dew point

      ≤0.1℃

      precision

      SO2+SOF2H2S、HF

      measurement value ≤ 10 μL/L, error≤±0.5 μL/L

      measured value > 10 μL/L, error±5%.

      CO、NO、N2O、NF3

      measurement value≤ 50 μL/L, error≤±2.0 μL/L

      measurement value > 50 μL/L, error≤±4%

      SF6

      Pure gas ≤ ± 0.1% (W/W)

      Air mix ≤ ± 0.5%

      N2

      ≤±0.5%

      \

      ≤±0.5%

      CF4

      \

      ≤±0.5%

      ≤±0.5%

      O2

      ≤±0.05%

      Dew point: resistance/mirror

      ≤±1℃/0.3℃

      repeatability

      SO2+SOF2、H2S、HF

      measured value ≤ 10 μL/L, ≤ 0.2 μL/L

      10μL/L~100μL/L:2%.

      CO、NO、N2O、NF3

      measured value  ≤ 50 μL/L, ≤ 1.5 μL/L

      detection value 50 μL/L ~1000 μL/L: ≤ 3%

      SF6

      pure gas

      ≤0.05%(W/W,RSD)

      air mix

      ≤1.0%(RSD)

      O2

      ≤1.0%(RSD)

      N2

      ≤1.0%(RSD)

      \

      ≤1.0%(RSD)

      CF4

      \

      ≤1.0%(RSD)

      ≤1.0%(RSD)

      dew point

      1%

      range

      SO2+SOF2

      0~100μL/L,0~2000μL/L

      H2S

      0~100μL/L

      HF

      0~20μL/L

      CO、NO、N2O、NF3

      0~1000μL/L

      SF6

      0~100%

      N2

      0~100%

      \

      0~100%

      CF4

      \

      0~80%

      0~80%

      O2

      0~1%

      dew point

      -80 ℃~ + 20 ℃ (resistance and capacitance)/-60 ℃~ + 20 ℃ (mirror)

      gas flow rate

      Decomposition, mixing ratio

      200±5%mL/Min  

      moisture

      500±10%mL/Min   


      Related recommendations

      JHRX series, infrared thermal imaging cameras

      Expert-level native analysis capabilities assist in diagnosing equipment status

      JHSP-30 SF6 Portable Helium Ion Detector

      Highly integrated all-in-one design

      JHZW-100, UV Imager

      All-day blind ultraviolet imaging technology

      JHYQ-1 Rapid Detector for Dissolved Gas Acetylene in Oil

      Adopt the principle of electrochemical detection

      Add wechat

      Scan and add customer service wechat